6 Emergency electrical power supply plant 6.1 General 6.1.1 Engine generator set 6.1.1.1 The emergency electrical power supply shall be provided by a generator set or sets driven by an engine located a) on the same property as the building it supplies or on an adjoining property; or b) on the health care facility’s premises, where a generator set is required for emergency power supply to essential electrical systems in conformance with CSA Z32. 6.1.1.2 The minimum engine generator set full load rating shall a) meet or exceed the calculated maximum site design load. Note: Refer to the definition of “maximum site design load” in Clause 3. b) be rated, as a minimum, prime power when a generator set is intended for installation in Class A or Class B HCFs; and c) be rated, as a minimum, emergency standby power when a generator set is intended for installation in a building defined as a Class C HCF or in a building which is not defined as an HCF. Note: See Clause B.3 for commentary on this Clause. 6.1.1.3 The generator set shall be capable of operating at 100% of the maximum site design load in an ambient temperature of 40 °C without overheating or suffering other detrimental effects. If operation above 40 °C is unavoidable, the generator system shall be designed and rated to operate at 100% maximum site design load at the higher operating temperature. Note: See Clause B.4 for commentary on this Clause.
6.1.2.2 The circuits supplying equipment intended to support continued operation of cooling system for the prime mover shall be connected ahead of the generator disconnecting means and overcurrent devices. 6.2 Location Note: See Clause B.5 for commentary on this Clause. 6.2.1 The emergency electrical supply system shall be located a) in a separate service room or rooms in a building separated from the remainder of the building by a fire separation with a fire-resistance rating in accordance with the requirements of Clause 5.2; or b) in a separate service room or enclosure outside the building located in accordance with the NBCC. The enclosure shall provide the following protection and security for the emergency electrical supply system: i) The enclosure shall be structurally adequate to resist flood, snow, wind, and shall be vandal- proof. The enclosure shall be braced for seismic forces where required by NBCC. ii) The enclosure shall be weatherproof and insulated to achieve the ambient temperature requirement of Clause 6.8.1 to maintain the system in an operable condition and prevent problems due to condensation and corrosion. iii) The enclosure shall provide adequate clearances as specified in Clause 6.5.1. iv) The enclosure structure shall have provision for electrical grounding in addition to the electrical equipment within the enclosure. v) The enclosure shall have provision for quick entry to authorized personnel. 6.2.2 Where an emergency electrical power supply system is required in conformance with CSA Z32, it shall be located within one storey of grade.
6.4.2 The generator set shall be capable of maintaining the emergency supply voltage and frequency such that a) on the one-step application of maximum site design load, the emergency electrical power supply system shall continue operating and returns to stable voltage and frequency within 10 s, in accordance with Clause 10.3.3; b) on application or removal of any load or group of loads, the resulting engine generator set voltage and frequency variation shall be within the range suitable for the connected equipment, with a return to stable voltage and frequency within a time frame suitable for the connected equipment; and c) where an emergency electrical power supply system is required for emergency power supply to essential electrical systems in conformance with CSA Z32, it shall be capable of maintaining a stable supply voltage for any load connected to the generator up to the maximum load that can be applied at one time in accordance with the control sequence for the emergency electrical power supply. The reduction in frequency shall not exceed 10% and the duration shall not exceed 3 s. 6.4.3 The generator, exciter, and voltage regulator shall be capable of supporting any non-linear loads that are connected to the emergency electrical power distribution system. The connection of non-linear loads to the generator shall be restricted to prevent undue generator voltage distortion that could adversely affect the operation of emergency loads or of the generator or its controls and protective devices. Note: See Clause B.6 for commentary on this Clause.CSA C282:19 pdf download.

Leave a Reply

Your email address will not be published. Required fields are marked *